EasySolar-II GX
EasySolar-II GX
The all-in-one solar power solution
The Victron EasySolar-II GX integrates the following elements:
• A MultiPlus-II inverter/charger
• A SmartSolar MPPT -Tr solar charge controller
• A GX device with a 2 x 16-character display.
These elements come prewired together inside a single unit. This greatly simplifies most installations, saving time and money.
KEY FEATURES
The all-in-one solar power solutionThe Victron EasySolar-II GX integrates the following elements:
These elements come prewired together inside a single unit. This greatly simplifies most installations, saving time and money. |
|
Display and Wi-FiThe display reads battery, inverter and solar charge controller parameters. The same parameters can be accessed with a smartphone or other Wi-Fi enabled device. In addition, Wi-Fi can be used to set up the system and to change settings. |
|
Solar charge controllerThe DC output of the SmartSolar MPPT is parallel wired with the DC connection of the MultiPlus-II inverter/charger. The on/ off mechanism of the MultiPlus-II also controls the SmartSolar MPPT. |
|
GX deviceThe integrated GX device includes:
The GX device controls the MultiPlus-II and the SmartSolar MPPT with respectively a VE.Bus and a VE.Direct connection. EasySolar-II GX 3 kVA |
KEY FEATURES
|
The all-in-one solar power solutionThe Victron EasySolar-II GX integrates the following elements:
These elements come prewired together inside a single unit. This greatly simplifies most installations, saving time and money. |
Display and Wi-FiThe display reads battery, inverter and solar charge controller parameters. The same parameters can be accessed with a smartphone or other Wi-Fi enabled device. In addition, Wi-Fi can be used to set up the system and to change settings. |
|
Solar charge controllerThe DC output of the SmartSolar MPPT is parallel wired with the DC connection of the MultiPlus-II inverter/charger. The on/ off mechanism of the MultiPlus-II also controls the SmartSolar MPPT. |
GX deviceThe integrated GX device includes:
The GX device controls the MultiPlus-II and the SmartSolar MPPT with respectively a VE.Bus and a VE.Direct connection. EasySolar-II GX 3 kVA |
FEATURES
VRM app for Wi-FiMonitor and manage your Victron Energy system from your smart phone and tablet. Available for both iOS and Android. |
VRM PortalOur free remote monitoring website (VRM) will display all your system data in a comprehensive graphical format. System settings can be changed remotely via the portal. Alarms can be received by e-mail. |
Grid in-line topologyThe EasySolar-II GX will use excess PV power to charge the batteries or to feed power back into the grid and will discharge the battery or use power from the grid to supplement a shortage of PV power. In case of a power outage, the EasySolar-II GX will disconnect the grid and continue to supply the loads. Loads that should shut down when AC input power is not available can be connected to a second output (not shown). These loads will be taken into account by the PowerControl and PowerAssist function in order to limit AC input current to a safe value. |
|
Grid parallel topologyThe EasySolar-II GX will use data from the external AC current sensor (must be ordered separately) or power meter to optimise self-consumption and, if required, to prevent grid feed. In case of a power outage, the EasySolar-II GX will continue to supply the critical loads. |
|
|
Current sensor 100A:50mATo implement PowerControl and PowerAssist and to optimise self-consumption with external current sensing. |
FEATURES
VRM app for Wi-FiMonitor and manage your Victron Energy system from your smart phone and tablet. Available for both iOS and Android. |
|
VRM PortalOur free remote monitoring website (VRM) will display all your system data in a comprehensive graphical format. System settings can be changed remotely via the portal. Alarms can be received by e-mail. |
Grid in-line topologyThe EasySolar-II GX will use excess PV power to charge the batteries or to feed power back into the grid and will discharge the battery or use power from the grid to supplement a shortage of PV power. In case of a power outage, the EasySolar-II GX will disconnect the grid and continue to supply the loads. Loads that should shut down when AC input power is not available can be connected to a second output (not shown). These loads will be taken into account by the PowerControl and PowerAssist function in order to limit AC input current to a safe value. |
|
Grid parallel topologyThe EasySolar-II GX will use data from the external AC current sensor (must be ordered separately) or power meter to optimise self-consumption and, if required, to prevent grid feed. In case of a power outage, the EasySolar-II GX will continue to supply the critical loads. |
|
Current sensor 100A:50mATo implement PowerControl and PowerAssist and to optimise self-consumption with external current sensing. |
SPECIFICATIONS
EasySolar-II |
24/3000/70-32 MPPT 250/70 GX |
48/3000/35-32 MPPT 250/70 GX |
48/5000/70-50 MPPT 250/100 GX |
INVERTER/CHARGER |
|||
PowerControl & PowerAssist |
Yes | ||
Transfer switch |
32 A |
50 A |
|
Maximum AC input current |
32 A |
50 A |
|
Auxiliary output |
32 A |
50 A |
|
INVERTER |
|||
Input voltage range |
19 – 33 V |
38 – 66 V |
38 – 66 V |
Output |
Output voltage: 230 VAC ± 2 % Frequency: 50 Hz ± 0,1 %1 |
||
Cont. output power at 25 °C3 |
3000 VA / 2400 W |
3000 VA / 2400 W |
5000 VA / 4000 W |
Cont. output power at 40 °C / 55 °C |
2200 W / 1700 W |
2200 W / 1700 W |
3700 W / 3000 W |
Maximum apparent feed-in power |
2470W / 3000 VA |
2470W / 3000 VA |
4400 W / 5000 VA |
Peak power |
5500 W |
5500 W |
9000 W |
Maximum efficiency |
94% |
95% |
96% |
Zero load power |
13 W |
11 W |
18 W |
Zero load power in AES mode |
9W |
7W |
12 W |
Zero load power in Search mode |
3W |
2W |
2W |
CHARGER |
|||
AC Input |
Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz |
||
Charge voltage ‘absorption’ |
28.8 V |
57.6 V |
|
Charge voltage ‘float’ |
27.6 V |
55.2 V |
|
Storage mode |
26.4 V |
52.8 V |
|
Maximum battery charge current |
70 A |
35 A |
70 A |
Battery temperature sensor |
Yes |
||
Programmable relay4 |
Yes |
||
Protection2 |
a-g |
||
VE.Bus communication port |
For parallel and three phase operation, remote monitoring and system integration |
||
General purpose com. port |
Yes, 2x |
||
SMARTSOLAR CHARGE CONTROLLER |
|||
Model |
MPPT 250/70-Tr |
MPPT 250/100-Tr |
|
Maximum output current |
70 A |
100 A |
|
Maximum PV power |
2000 W |
4000 W |
5800 W |
Maximum PV open circuit voltage |
250 V |
||
Maximum efficiency |
99% |
||
Self-consumption |
20 mA |
||
Charge voltage ‘absorption’, default |
57.6 V |
||
Charge voltage ‘float’, default |
55.2 V |
||
Protection2 |
a–e |
||
GENERAL |
|||
Interfaces |
BMS-Can, USB, Ethernet, VE.Direct, Wi-Fi |
||
Remote on-off |
Yes |
||
Operating temp. range |
-40 to +55 °C (fan assisted cooling) Max. altitude 2000 m |
||
Humidity (non-condensing) |
max 95 % |
||
ENCLOSURE |
|||
Material & Colour |
aluminium (blue RAL 5012) |
||
Protection category |
IP21 |
||
Battery-connection |
M8 bolts |
||
PV connection |
M6 bolts |
||
230 VAC-connection |
Screw terminals 16 mm2 (6 AWG) |
||
Weight |
26 kg |
26 kg |
38.6 kg |
Dimensions (h x w x d) mm |
499 x 268 x 237 |
604 x 323 x 253 |
|
STANDARDS |
|||
Safety |
EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2 |
||
Emission / Immunity |
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 |
1. Can be adjusted to 60 Hz
2. Protection key: a) output short circuit, b) overload, c) battery voltage too high, d) battery voltage too low, e) temperature too high, f) 230 VAC on inverter output, g) input voltage ripple too high
3. Non-linear load, crest factor 3:1
4. Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating: 230 V / 4 A, DC rating: 4 A up to 35 VDC and 1 A up to 60 VDC
SPECIFICATIONS
EasySolar-II
INVERTER/CHARGER:
24/3000/70-32 MPPT 250/70 GX
PowerControl & PowerAssist: Yes
Transfer switch: 32A
Maximum AC input current: 32A
Auxiliary output: 32A
48/3000/35-32 MPPT 250/70 GX
PowerControl & PowerAssist: Yes
Transfer switch: 32A
Maximum AC input current: 32A
Auxiliary output: 32A
48/5000/70-50 MPPT 250/100 GX
PowerControl & PowerAssist: Yes
Transfer switch: 50A
Maximum AC input current: 50A
Auxiliary output: 50A
INVERTER:
24/3000/70-32 MPPT 250/70 GX
Input voltage range: 19 – 33 V
Output: Output voltage: 230 VAC ± 2 % Frequency: 50 Hz ± 0,1 %1
Cont. output power at 25 °C3: 3000 VA / 2400 W
Cont. output power at 40 °C / 55 °C: 2200 W / 1700 W
Maximum apparent feed-in power: 2470W / 3000 VA
Peak power: 5500 W
Maximum efficiency: 94 %
Zero load power: 13 W
Zero load power in AES mode: 9W
Zero load power in Search mode: 3W
48/3000/35-32 MPPT 250/70 GX
Input voltage range: 38 – 66 V
Output: Output voltage: 230 VAC ± 2 % Frequency: 50 Hz ± 0,1 %1
Cont. output power at 25 °C3: 3000 VA / 2400 W
Cont. output power at 40 °C / 55 °C: 2200 W / 1700 W
Maximum apparent feed-in power: 2470W / 3000 VA
Peak power: 5500 W
Maximum efficiency: 95 %
Zero load power: 11 W
Zero load power in AES mode: 7W
Zero load power in Search mode: 2W
48/5000/70-50 MPPT 250/100 GX
Input voltage range: 38 – 66 V
Output: Output voltage: 230 VAC ± 2 % Frequency: 50 Hz ± 0,1 %1
Cont. output power at 25 °C3: 5000 VA / 4000 W
Cont. output power at 40 °C / 55 °C: 3700 W / 3000 W
Maximum apparent feed-in power: 4400 W / 5000 VA
Peak power: 9000 W
Maximum efficiency: 96 %
Zero load power: 18 W
Zero load power in AES mode: 12W
Zero load power in Search mode: 2W
CHARGER:
24/3000/70-32 MPPT 250/70 GX
AC Input: Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz
Charge voltage ‘absorption’: 28.8 V
Charge voltage ‘float’: 27.6 V
Storage mode: 26.4 V
Maximum battery charge current: 70 A
Battery temperature sensor: Yes
Programmable relay4: Yes
Protection2: a-g
VE.Bus communication port: For parallel and three phase operation, remote monitoring and system integration
General purpose com. port: Yes, 2x
48/3000/35-32 MPPT 250/70 GX
AC Input: Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz
Charge voltage ‘absorption’: 57.6 V
Charge voltage ‘float’: 55.2 V
Storage mode: 52.8 V
Maximum battery charge current: 35 A
Battery temperature sensor: Yes
Programmable relay4: Yes
Protection2: a-g
VE.Bus communication port: For parallel and three phase operation, remote monitoring and system integration
General purpose com. port: Yes, 2x
48/5000/70-50 MPPT 250/100 GX
AC Input: Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz
Charge voltage ‘absorption’: 57.6 V
Charge voltage ‘float’: 55.2 V
Storage mode: 52.8 V
Maximum battery charge current: 70 A
Battery temperature sensor: Yes
Programmable relay4: Yes
Protection2: a-g
VE.Bus communication port: For parallel and three phase operation, remote monitoring and system integration
General purpose com. port: Yes, 2x
SMARTSOLAR CHARGE CONTROLLER:
24/3000/70-32 MPPT 250/70 GX
Model: MPPT 250/70-Tr
Maximum output current: 70 A
Maximum PV power: 2000 W
Maximum PV open circuit voltage: 250 V
Maximum efficiency: 99%
Self-consumption: 20 mA
Charge voltage ‘absorption’, default: 57.6 V
Charge voltage ‘float’, default: 55.2 V
Protection2: a–e
48/3000/35-32 MPPT 250/70 GX
Model: MPPT 250/70-Tr
Maximum output current: 70 A
Maximum PV power: 4000 W
Maximum PV open circuit voltage: 250 V
Maximum efficiency: 99%
Self-consumption: 20 mA
Charge voltage ‘absorption’, default: 57.6 V
Charge voltage ‘float’, default: 55.2 V
Protection2: a–e
48/5000/70-50 MPPT 250/100 GX
Model: MPPT 250/100-Tr
Maximum output current: 100 A
Maximum PV power: 5800 W
Maximum PV open circuit voltage: 250 V
Maximum efficiency: 99%
Self-consumption: 20 mA
Charge voltage ‘absorption’, default: 57.6 V
Charge voltage ‘float’, default: 55.2 V
Protection2: a–e
GENERAL:
24/3000/70-32 MPPT 250/70 GX
Interfaces: BMS-Can, USB, Ethernet, VE.Direct, Wi-Fi
Remote on-off: Yes
Operating temp. range: -40 to +55 °C (fan assisted cooling) Max. altitude 2000 m
Humidity (non-condensing): max 95 %
48/3000/35-32 MPPT 250/70 GX:
Interfaces: BMS-Can, USB, Ethernet, VE.Direct, Wi-Fi
Remote on-off: Yes
Operating temp. range: -40 to +55 °C (fan assisted cooling) Max. altitude 2000 m
Humidity (non-condensing): max 95 %
48/5000/70-50 MPPT 250/100 GX
Interfaces: BMS-Can, USB, Ethernet, VE.Direct, Wi-Fi
Remote on-off: Yes
Operating temp. range: -40 to +55 °C (fan assisted cooling) Max. altitude 2000 m
Humidity (non-condensing): max 95 %
ENCLOSURE:
24/3000/70-32 MPPT 250/70 GX:
Material & Colour: aluminium (blue RAL 5012)
Protection category: IP21
Battery-connection: M8 bolts
PV connection: M6 bolts
230 VAC-connection: Screw terminals 16 mm2
(6 AWG)
Weight: 26 kg
Dimensions (h x w x d) mm: 499 x 268 x 237
48/3000/35-32 MPPT 250/70 GX:
Material & Colour: aluminium (blue RAL 5012)
Protection category: IP21
Battery-connection: M8 bolts
PV connection: M6 bolts
230 VAC-connection: Screw terminals 16 mm2
(6 AWG)
Weight: 26 kg
Dimensions (h x w x d) mm: 499 x 268 x 237
48/5000/70-50 MPPT 250/100 GX:
Material & Colour: aluminium (blue RAL 5012)
Protection category: IP21
Battery-connection: M8 bolts
PV connection: M6 bolts
230 VAC-connection: Screw terminals 16 mm2
(6 AWG)
Weight: 38.6 kg
Dimensions (h x w x d) mm: 604 x 323 x 253
STANDARDS
24/3000/70-32 MPPT 250/70 GX:
Safety: EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2
Emission / Immunity: EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1,IEC 61000-6-2, IEC 61000-6-3
48/3000/35-32 MPPT 250/70 GX:
Safety: EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2
Emission / Immunity: EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
48/5000/70-50 MPPT 250/100 GX:
Safety: EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2
Emission / Immunity: EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
1. Can be adjusted to 60 Hz
2. Protection key: a) output short circuit, b) overload, c) battery voltage too high, d) battery voltage too low, e) temperature too high, f) 230 VAC on inverter output, g) input voltage ripple too high
3. Non-linear load, crest factor 3:1
4. Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating: 230 V / 4 A, DC rating: 4 A up to 35 VDC and 1 A up to 60 VDC